An Algorithm for Detecting CT Saturation

변류기 2차전류의 포화 여부 판단 알고리즘

  • Published : 2001.06.01

Abstract

This paper presents an algorithm for detecting current transformer (CT) saturation. At the instants of beginning (or end) of saturation, as a magnetizing inductance of the core is changed significantly, the shapes of the secondary current are also changed significantly though secondary currents are continuous the instants. At the instants, the second-order of third-order difference of the secondary current has big values. Thus, the third difference of the current is used to detect the beginning/end of CT saturation in this paper. If the magnitude of third-order difference of the secondary current is larger than a threshold value, the CT begins of ends saturation at the instants. The proposed detection method is unaffected by the amount of residual flux. The results of various tests with residual flux from -80% to +80% indicate satisfactory performance of the method.

Keywords

References

  1. M. S. Sachdev, T. S. Sidhu, H. S. Gill, 'A Busbar Protection Technique and Its Performance During Saturation and CT Ratio-Mismatch,' IEEE Trans. on PWRD, Vol. 15, No. 3, July 2000, pp. 895-901 https://doi.org/10.1109/61.871349
  2. G. Hosemann, H. M. Steigerwald, 'Modal Saturation Detector for Digital Differential Protection,' IEEE Trans. on PWRD, Vol. 8, No. 3, July 1993, pp. 933-940 https://doi.org/10.1109/61.252620