The Study on Characteristics of Water Spray and Droplet from Fire Sprinkler Head

소화용 스프링클러 헤드의 살수분포 및 수적 특성에 대한 연구

  • 추병길 (순천제일대학 산업안전관리과) ;
  • 최종욱 (포항제철 기술연구소) ;
  • 차경세 (전남대학교 대학원)
  • Published : 2001.06.01

Abstract

The effect of water spray for the fire sprinkler depends on droples distribution over maximum possible floor area. The present study are carried out for the characteristics of water spray and droplets experimentally and numerically km two fire sprinkler heads which are CHM head and CHl heal CHl head is self-production and CHl head is widely used up to date. As the result of using CHM head, water spray and droplets are distributed over large area because CHM head has smooth surface and non-flamed shape. When the pressure of fire sprinkler head is low, SMD(sauter mean diameter) is large and when the pressure of fire sprinkler head is high, SMD is small.

Keywords