Journal of the Korean Society of Safety (한국안전학회지)
- Volume 16 Issue 1
- /
- Pages.1-8
- /
- 2001
- /
- 1738-3803(pISSN)
- /
- 2383-9953(eISSN)
The Development of UV-IR Combination Flame Detector
UV-IR 복합형 화재감지장치 개발
Abstract
All objects emit thermal radiation and this radiation is the basis of the techniques used to detect flames. The usual phenomena occurring in the initial stage of the fire are generally invisible products of a combustion and visible smoke. Liquid or gaseous materials do not undergo a smoldering stage so that fires develop very rapidly. Also, the heat generated by the initial flames is usually not sufficient to activate a heat detector. In this case the most effective criterion for automatic fire detection is the flame. According to the fire regulation of korea, the compulsory standard provided that a flame detector shall be installed in a place that the attachment height of detector is higher than 20 m, chemical plants, hangar, refinery, etc.. The results of the research and development are discriminated between a flame and other radiant emitters, developed a UV detector tube contains an inert gas which absorbs UV radiation, developed PZT pyroelectric element is based on the use of photovoltanic cell, developed IR band-pass filter that only allow a 4.3
Keywords
- spectrum of carbonaceous fire;
- UV detector tube;
- PZT;
- IR bandpass filter;
- UV-IR combination flame detector