가변 풍량 유닛에 의한 실내 공간의 온도제어를 위한 공간의 분할 모델과 상태궤환 제어기의 개발에 관한 연구

  • 박세화 (마이크로인스펙션(주) 측정기술연구소) ;
  • 신승철 (전자통신연구원 원천기술본부)
  • Published : 2001.10.01

Abstract

We propose a control scheme to control the indoor zone temperature via variable air volume (VAV) unit. To control the room temperature, state space model of the conditioned zone which is partitioned into nine artificial sectional regions is derived. The nonlinearity of the damper motion and actuator are considered for the practical use in the state space system description. The temperature control of the room temperature is performed by manipulating the degree of openness of the damper in relation to the local room temperature and the supplied air flow rate. In general, since a local temperature in the conditioned zone is measured, it is required to estimate the temperature values in each regions for the precise temperature control. We thus design a state observer to estimate the regional temperature, and use these values in the controller. The overall control system consists of the state observer based state feedback with the integral control. We compared the control results of the proposed scheme with those of cascade proportional and integral (PI) control, and showed that the scheme achieved precise control of the conditioned system.

Keywords

References

  1. Heating, Ventilating and Air Conditioning Clifford, G. E.
  2. Variable Air Volume Systems for Environmental Quality Chen, S. Y. S.;Demster, S. J.
  3. Variable Air Volume manual Wendes, H.
  4. Korean Journal of air-Conditioning and Refrigeration Engineering v.18 no.4 Control of Variable Air Volume System Choi, H. K.
  5. Ventilating and Air conditioning Control Systems for Heating Haines, R. W.;Hittle, D. C.
  6. Temperature Control in Large Buildings Federspiel, C. C.
  7. Journal of Industrial Technology v.3 no.1 Development of a Distributed Controller with Controller Area Network and Application to the Control of a Variable Air Volume Unit Park, S. -H.;Cheon, K. -S.
  8. Energy simulation in building design Clarke, J. A.
  9. ASHARAE Transaction: Research v.3546 Parametric analysis of a building space conditioned by a VAV system Zhang, Z.;Nelson, R. M.
  10. Journal of Industrial Technology v.1 no.1 State Space Modeling of Simplified Zone Thermal Dynamics for the Control of Variable Air Volume Unit Park, S. -H.
  11. Discrete Time Control Systems Ogata, K.
  12. Control Engineering Practice v.8 no.7 On self-tuning control of electromagnetic levitation systems Lee, S. H.;Sung, H. K.;Lim, J. T.;Bien, Z.
  13. Linear system theory and design Chen, C. -T.