Comparative Performance Evaluation of Lightning Air Terminals by the HV Laboratory Test

고전압 모의시험을 통한 피뢰침의 성능 비교평가

  • Published : 2001.12.01

Abstract

There are claims that ESE(Early streamer emission) Air terminals offer a vastly increased zone of protection over that of traditional lightning rods by causing the emission of an upward streamer/leader that will propagate towards the tip of downward leader at an early stage in the attachment process than would occur for a simple rod in the same geometrical configurations. This paper shows the results of comparing test a particular type of ESE air terminals with a simple rod conducted in the KEH HV laboratory, which are lightning impulse voltage test, flashover direction test and corona emission current measurement. The results from this test show a completely random scattering of flashovers to the conventional and ESE air terminals under identical electrics] and geometrical conditions, and thus shows no advantage of one terminal over the other.

Keywords

References

  1. H. Armstrong and E. Whitehead, 'Field and Analytical Studies of Transmission Line Shielding', IEEE Trans PAS, Vol.87, No.1, Jan., 1968 https://doi.org/10.1109/TPAS.1968.291999
  2. R. H. Lee, 'Lightning Protection of Buildings', IEEE Trans. on lA, Vol.IA-15, No. 3, pp.236-240, May/June 1979
  3. NFPA 780-1997, Standard for the Installation of Lightning Protection Systems
  4. IEC 61024-1-2 : 1985, Protection of Structures against Lightning : Part 1-2 : General Principles
  5. K. Katoh et al., 'Working Principles of Prevectrons : Theory and Practices', Workshop on Physics of Lightning', pp.73-74, IWPL2001
  6. DUBAL MESSIEN Company, Satelit+ ESE Manual
  7. A. Rousseu et al. 'Which Test for E.S.E. Lightning Conductors?', Proceedings of 10th. International Symposium on HV. Eng, Montreal(Canada), pp.273-277, August 25-29, 1997
  8. G. Berger, 'Determination of the Inception Electric Field of the Lightning Upward Leader', Proceedings. of 8th. International Symposium on HV. Eng, Yokohama(Japan), paper 70.02, 1993
  9. K.P. Heary et al. 'An Experimental Study of Ionizing Air terminal Performance', IEEE 88 SM. 572-0
  10. NF C 17-102-July 1995, Llightning Protection of Structures and Open Areas against Lightning using ESE Air Terminals
  11. T. Suzuki, K. Miyake, I. Kishizima, 'Studies on Experimental Simulation of Lightning'. IEEE PAS., Vol.PAS-100, No. 4, pp.1703-1711, April 1981 https://doi.org/10.1109/TPAS.1981.316507
  12. P. Chowdhuri, Electromagnetic Transient in Power Systems, RSP LTD, pp.229-232, 1996
  13. F. D'Alessandro, G.Beger, 'Laboratory Studies of Corona Current Emissions from Blunt, Sharp and Multipointed Air Terminals', ICLP-98, 4b.2, pp.418-424, 1998
  14. S. Grzybowski, et al., 'Comparative Testing of Ionizing and Non-ionizing Air Terminals', 10th. Inter. Sym. on HV. Eng, Montreal(Canada), pp.331 -334, August 25-29. 1997.c