바닥복사 난방시스템의 제어방식에 관한 실험적 연구

An Experimental Study on the Control Methods of Radiant Floor Heating Systems

  • 발행 : 2001.12.01

초록

In this study, existing control methods that are suggested or applied until now are classified by control parameters, and stability of in the room and floor surface temperatures of each control method is compared through experiments. Then, the control performance of these control methods are analyzed to evaluate the applicability to Korean apartment housing. From the result of the applicability analysis, the outdoor reset with on/off PWM control is found to be desirable for district heating systems and flux modulation is found to be applicable for decentralized heating systems. In the case of independent control systems for each room, on/off PWM control is desirable.

키워드

참고문헌

  1. ASHRAE Transactions The Temperature Stability of a Radiant Slab-on-grade MacCluer C.R.
  2. Doctoral dissertation An Experimental Approach for Evaluating Contol Strategies of Hydronic Radiant Floor Heating Systems Leigh S.B.