Improvement of Breakdown Characteristics Using Ribbed Spacer of GIS

GIS 립 스페이서에 의한 파괴전압 특성 개선

  • Published : 2001.09.01

Abstract

This paper describes the effect of various conditions of the ribs on the breakdown characteristics when metal particle is attached to the spacer in GIS. More improved spacer shape in breakdown characteristics than conventional one is proposed by comparing the results acquired by varying location, length and thickness of the ribbed spacer. As a result, it was found that the electrical breakdown characteristics of the spacer with two ribs were generally better than that with only one rib or no ribs, and it was dependent on the rib length and rib thickness. Especially, it was also confirmed that the electrical breakdown characteristics were more improved by rounding the rib edge.

본 논문에서는 금속성 파티클이 GIS 스페이서에 부착되었을 경우 파괴전압특성에 대한 립의 여러 조건에서의 효과를 분석하였다. 립-스페이서의 여러 위치에 금속성 파티클을 부착하고 립의 위치, 길이, 두께 등의 변화에 따른 파괴전압을 측정하여 기조에 제안된 립-스페이서보다 파괴전압을 더욱 향상시킬 수 있는 형상을 제시하고자 하였다. 그 결과 립이 없거나 립이 하나인 스페이서 보다 립이 두 개 있는 형태의 립-스페이서가 전반적으로 가장 양호한 파괴전압 특성을 가지고 있음을 알 수 있었으며, 립의 길이와 두께에 따라서도 파괴전압 특성이 달라짐을 알 수 있었다. 특히 립의 끝단을 라운드 처리함으로써 파괴전압 특성을 더욱 향상시킬 수 있음을 알 수 있었다.

Keywords

References

  1. 변전설비 진단기술 개발 연구(최종보고서) 권동진 외
  2. CIS 무정전 점검기법 연구(최종보고서) 윤덕량 외
  3. Japan-Korea Symposium on ED and HVE Enhancement of Insulation Reliability of CIS Fumihiro Endo(et al.)
  4. IEEE Transactions on Power Delivery v.3 no.3 Particle-initiated Breakdown Characteristics on Ribbed Spacer Surface For SF6 Gas Insulated Switchgear Tokio Yamagiwa(et al.)
  5. 대한전기학회 방전 및 고전압연구 춘계학술발표대회 논문집 CIS 립-스페이서의 형상에 대한 전계해석 및 파괴전압특성 류성식;곽희로 외
  6. 대한전기학회 하계학술대회 논문집 v.C 개선된 CIS 스페이서의 전계해석 및 파괴전압 특성 류성식;곽희로 외
  7. 현대중공업 연구보고서 756kV CIS 기초설계기술 개발 김익모 외
  8. IEEE Trans. on Electrical Insulation v.日-22 no.4 Spacer Involvement in Conducting Particle-initiated Breakdown in Compressed Gas Insulated Systems A. K. Chakrabarti(et al.)