A Study on the Prevention of Crack Generated in Interface Cu and Epoxy with Painting of Carbon

카본 도포에 따른 Cu-Epoxy 접촉면에서 발생하는 크랙방지에 관한 연구

  • 송재주 (순천청암대학 컴퓨터정보과학부 전기통신과) ;
  • 김성훈 (순천청암대학 컴퓨터정보과학부 전기통신과) ;
  • 황종선 (담양대학 전기전자공학부) ;
  • 박종광 (전북대학교 전기공학과) ;
  • 한병성 (전북대학교 전기공학과)
  • Published : 2001.07.01

Abstract

The bushing for high voltage and large and power should endure weight of itself and force of pushing from contact with circuit breaker. Like this, epoxy mold bushing has to be strong without fault. However, the external circumstances and internal factors was caused by partial discharge, flashover and dielectric breakdown. Therefore, to remove external factor of defect and to prevent the internal cracks and cavity generated from the contraction on interface of Cu-Epoxy, we should form semi-conductive layer on Cu bar by carbon. Then, the PD properties and the insulation qualities of epoxy mold type bushing was able to improved by roles of cushions for the direction of diameter and by effects fo natural sliding like as separated from conductor for the direction of length. So, in this work, we could prove the method of semi-conductive layer in making the long conductor.

Keywords

References

  1. 93 International Conference on Advanced Composites Materials Advanced Composites T. Candra;A. K. Dhingra
  2. KIEEME v.1 no.1 The Crack Resistance and Dielectric Breakdown Properties of Epoxy Composites due to the Multi Stresses Variation B. C. Song(et al.)
  3. 誘電體 現象論 家田正之
  4. IEEE Trans, on Elec. Insul. v.23 no.2 Partial Discharge Measured with an Automatic System in Epoxy Resin and PE U. Bammert(et al.)
  5. IEEE Trans. on Elec. Insul. v.El-15 no.3 Dielectric Breakdown Process of Polymers M. Ieda
  6. KIEEME v.1 no.2 A Study on the reduction of PD generated in the PT for 25.8 kV J. J. Song
  7. 전기전자재료학회지 v.10 no.3 부분방전 전하와 음향방출 펄스의 동시 측정에 의한 트리잉 파괴 진단 김성홍(외2명)