Simulation for Chlorine Residuals and Effect of Rechlorination in Drinking Water Distribution Systems of Suwon City

수원시 상수관망에서 잔류염소와 재염소주입의 효과 예측

  • Published : 2000.03.15

Abstract

Chlorine is widely used as a disinfectant in drinking-water systems throughout the world. Chlorine residual was used as an indicator for prediction of water quality in water distribution systems. The variation of chlorine residual in drinking water distribution systems of Suwon city was simulated using EPANET. EPANET is a computerized simulation model which predicts the dynamic hydraulic and water quality behavior within a water distribution system operating over an extended time period. Sampling and analysis were performed to calibrated the computer model in 1999 (Aug. Summer). Water quality variables used in simulations are temperature, roughness coefficient, pipe diameter, pipe length, water demand, velocity and so on. Extended water residence time affected water quality due to the extended reaction time in some areas. All area showed the higher concentration of chlorine residual than 0.2mg/l(standard). So it can be concluded that any area in Suwon city is not in biological regrowth problem. Rechlorination turned out to be an useful method for uniform concentration of free chlorine residual in distribution system. The cost of disinfectant could be saved remarkably by cutting down the initial chlorine concentration to the level which guarantees minimum concentration (0.2mg/l) throughout the distribution system.

Keywords