The effect of heat exchanger surface treatment on the frosting/defrosting behavior in a fin-tube heat exchanger is investigated experimentally. It is found that the hydrophilic surface mainly influences on the frosting behavior, however, the hydrophobic surface gives some influence on the defrosting behavior. In view of frosting performance, surface-treated heat exchanger with either hydrophilic or hydrophobic characteristic shows a little improvement in the thermal performance than the aluminium heat exchanger with no surface treatment. The result reveals that the heat exchanger with hydrophobic surface treatment is more effective in view of the defrosting efficiency and time. The amounts of residual water on the surface-treated heat exchangers are shown to be smaller than those of the bare heat exchanger, therefore further improvements on the performance of re-operations are expected.

Keywords

References

  1. Wang, C. C. and Chang, C. T., 1998, 'Heat and Mass Transfer for Plate Fin-and- Tube Heat Exchangers, with and without Hydrophilic Coating,' Int. J. Heat Mass Transfer, Vol. 41, No. 20, pp. 3109-3120 https://doi.org/10.1016/S0017-9310(98)00060-X
  2. Mimaki, M., 1987, 'Effectiveness of Finned Tube Heat Exchanger Coated Hydrophilic-type Film,' ASHRAE paper #3017 presented at January meeting
  3. Ostin, R. and Johannesson, G., 1991, 'A Polymetric Approach to Counteract Frosting in Air-to-air Heat Exchanger,' Heat Recovery Systems & CHP, Vol. 11, No.5, pp. 415-421 https://doi.org/10.1016/0890-4332(91)90009-S
  4. Seki, N., Fukusako, S., Matsuo, K., and Uemura, S., 1983, 'Incipient Phenomena of Frost Formation,' 日本機械學會論文集(B편), 50-451, pp. 825 - 830.
  5. Tsuda, Y. and Iwamoto, A., 1992, 'Anti-frosting Heat Exchanger,' National Technical Report, Vol. 38, No.1, pp. 108-113
  6. O'Neal, D. L., Bryant, J. A., and Parker, B., 1997, 'Impact of Hydrophobic Coating on the Frost Buildup and Defrost Performance of a Heat Pump Evaporator', 45th Oji International Seminar, pp. 181 -187
  7. 이관수, 김규우, 지성, 1998, '핀-관 열교환기에 대한 제상 거동에 관한 실험적 연구,' 공기조화.냉동공학회 논문집, Vol. 10, No. 6, pp.649-657
  8. Lee, K. S. and Kim, W. S., 1999, 'The Effects of Design and Operating Factors on the Frost Growth and Thermal Performance of a Flat Plate Fin-tube Heat Exchanger Under the Frosting Condition,' KSME International Journal, Vol. 13, No. 12, pp. 973-981
  9. Kline, S. J. and McClintock, F. A., 1953, 'Describing Uncertainties in Single-Sample Experiments,' Mechanical Engineering, Vol. 75, pp. 3-8
  10. Bryant, J. A., 1995, 'Effects of Hydrophobic Surface Treatments on Dropwise Condensation and Freezing of Water,' Ph.D. Thesis, Texas A&M University, USA
  11. Tao, Y. -X., Mao, Y., and Besant, R. W., 1994, 'Frost Growth Characteristics on Heat Exchanger Surfaces: Measurement and Simulation Studies,' HTD-Vol. 286, Fundamentals of Phase Change: Sublimation and Solidification, ASME
  12. Saito, H., Takai, K. and Takazawa, H., 1997, 'A Study of Adhesiveness of Wet Snowflakes for Water Repellent Surface,' 表面技術, Vol. 48, No. 2, pp. 105 - 106
  13. John, D. B, Issam, M., Christopher, B. W., and Elias, I. F., 1996, 'Contact Angle Temperature Dependence for Water Droplets on Practical Aluminum Surfaces,' Int. J Heat Mass Transfer, Vol. 40, No.5, pp. 1017- 1033 https://doi.org/10.1016/0017-9310(96)00184-6
  14. 이관수, 이태희, 김우승, 1995, '착상시 설계인자에 따른 핀-관 열교환기의 성능변화에 관한 실험적 연구, 대한기계학회 논문집,' Vol. 19, No. 10, pp. 2657-2666