An experimental study on heat transfer characteristics in the ice storage system of ice-on-coil type with rectangular finned tube during freezing process

직사각형 휜이 부착된 관외착빙형 빙축열조에서 응고과정시 열전달 특성에 관한 연구

  • Kwon, H.Y. (Graduate School, In-ha University) ;
  • Koh, J.Y. (Graduate School, In-ha University) ;
  • Jeong, B.Y. (Graduate School, In-ha University) ;
  • Yim, C.S. (Dept. of Mechanical Eng., In-ha University)
  • Published : 2000.12.31

Abstract

The purpose of this study is to improve heat transfer by attaching rectangular fins to tube. Experiments were carried out under the following conditions - Aspect ratio$(W_f/R_f)$ is 0.7, 1.2 and 1.8. Temperature conversion between high and low positions of water in the thermal storage appeared because maximum density point of water is about $4^{\circ}C$ and inlet direction of working fluid influenced conductive heat transfer Compared with the unfinned tube(bare tube), the rectangular tube increased the ice thermal storage energy and the ice thermal storage energy was increased as aspect ratio was increased.

Keywords