태양열 이용 냉난방 공조시스템의 재생성능에 영향을 미치는 인자의 기여율에 관한 연구

Study on the Contribution Ratio of Factors to Affect Regeneration Performance of a Solar Air Conditioning System

  • 김보철 (부경대학교 냉동공조공학과) ;
  • 최광환 (부경대학교 냉동공조공학과) ;
  • 금종수 (부경대학교 냉동공조공학과)
  • Kim, B.C. (Dept. of Refrigeration & Air-conditioning Eng., Pukyong National University) ;
  • Choi, K.H. (Dept. of Refrigeration & Air-conditioning Eng., Pukyong National University) ;
  • Kum, J.S. (Dept. of Refrigeration & Air-conditioning Eng., Pukyong National University)
  • 발행 : 2000.03.31

초록

This study was performed to find out how much experimental factors influence on regeneration performance in a solar air conditioning system. The experimental apparatus was set up in a climate-controlled chamber where temperature and humidity could be kept constant. In order. to investigate factors' influence on the regeneration performance of the solar air conditioning system, the model experiment was done using the 600mm $\times$ 600mm black painted aluminum regenerator. The design and analysis of experiment were done by the design of experiments, especially the table of orthogonal arrays. In order to find out how much experimental factors influence on regeneration performance, the table of orthogonal arrays $L_8(2^7)$ was used. According to the results, it was found that the most influential factor to affect regeneration performance was the concentration of LiCl solution. The next influential factors were a solar radiation, an air velocity, and the temperature of LiCl solution in order.

키워드