A study for Decision Method of Human Body Safety according to Power Load Fluctuation of the Chechon Area

제천지역 전력부하변동에 따른 인체 전 판단 방법에 대한 연구

  • Published : 2000.12.01

Abstract

This paper presents a study for decision method of human body safety according to power load fluctuation of the Chechon area. To cope with substantial electromagnetics analysis, the safety assessments were analyzed the double 154 [kV] T/L, 345 [kV] T/L, Chechon-Ichon, Chechon-Youngju, respectively. As the results of case study, in case of 345 [kV] T/L, the electric field value was 11.4927 [kV/m], magnetic field value was 0.4622 [G] at the point about 7 [m] away from the line in severest case. The results showed that the membership of a proposition fuzzy '11.4937 [kV/m] is hazardous' is 0.7063 for the severest case in case of 345 [kV] T/L. As the analytic results using the fuzzy qualifier term, the membership in case of very false is 0.0862 and fairly false is 0.5419, respectively.