The effect of surface contact angle on the behavior of frost formation in a fin-tube heat exchanger

핀-관 열교환기의 착상 거동에 대한 표면 접촉각의 영향

  • Published : 2000.01.01

Abstract

The effect of surface contact angle on the behavior of frost formation in a fin-tube heat exchanger is investigated experimentally. It is shown that both heat exchangers with hydrophilic and hydrophobic surfaces appear to have a better thermal performance than bare aluminium heat exchanger, but the improvements are very small. There is a little increase in the amount of the frost deposited onto the heat exchanger with both hydrophilic and hydrophobic surface. However, the effect of contact angle on the frost density is observed ; the frost with high density forms on the heat exchanger with hydrophilic surface ; and the frost with low density is deposited onto the heat exchanger with hydrophobic surface when compared with the frost deposited onto the heat exchanger with bare aluminium surface. This may be attributed to the fact that the shape of water droplets which condense on the surface of heat exchanger at the early stage of frosting varies with contact angle, and thus makes a difference on the structure of frost formation. From the experiments with different relative humidity of inlet air, it is shown that the variations of operating parameter make no influence on the effect of surface contact angle on the frosting behavior in the heat exchanger.

Keywords

References

  1. Trans. of JSME Effect of electric field on frosting phenomenon Munakata, T.;Yabe, A.;Tanasawa, I.
  2. Journal of Refrigeration no.2 Frost formation on the surface of refrigeration apparatus under electric fields Babakin, B. C.;Elykin, M. A.
  3. ASHRAE Transactions, CH-93-2-4 Performance improvement of plate fin-and-tube heat exchangers under frosting conditions Ogawa, K.;Tanaka, N.;Takeshita, M.
  4. Heat Recovery Systems & CHP v.11 no.5 A polymetric approach to counteract frosting in air-to-air heat exchanger Ostin, R.;Johannesson, G.
  5. 日本機械學會論文潗(B편) Incipient phenomena of frost formation Seki, N.;Fukusako, S.;Matsuo, K.;Uemura, S.
  6. National Technical Report v.38 no.1 Antifrosting Heat Exchanger Tsuda, Y.;Iwamoto, A.
  7. 45th Oji International Seminar Impact of hydrophobic coating on the frost buildup and defrost performance of a heat pump evaporator O'Neal, D. L.;Bryant, J. A.;Parker, B.
  8. 대한기계학회논문집(B) v.19 no.10 착상시 설계인자에 따른 핀-관 열교환기의 성능변화에 관한 실험적 연구 이관수;이태희;김우승
  9. Mechanical Engineering v.75 Describing uncertainties in single-sample experiments Kline, S. J.;McClintock, F. A.
  10. Effects of Hydrophobic Surface Treatments of Dropwise Condensation and Freezing of Water Bryant, J. A.