Development of Electronic Limit Switch for the Drive Unit of Incore Detector System Application

노내 핵계측 계통 구동기기의 전자식 한계스위치 개발

  • 박종범 (정회원, 한전 전력연구원) ;
  • 양승권 (정회원, 한전전력연구원) ;
  • 이상효 (정회원, 광운대학교 제어계측공학과)
  • Published : 2000.07.01

Abstract

In this paper, we study a cause of malfunction of switch to control drive motor in DFMS(Digital Flux Mapping System) which can measure incore neutron flux of the nuclear plant, and develope a method to solve this problem. DFMS has the type of generating contact signal by mechanical switch lever, which is operated whenever thimble detector inserted or withdrawed through thimble Guide Tube. However the characteristics of the lever tend to be changed by mechanical degrade or bad environment and the lever finally generates errotic contact signal. Therefore we installed electric coil ass'yin the outside of Guide Tube instead of mechanical switch assy's. In addition we applied resonance effect to control circuit and installed condenser in the input of power supply to protect noise and interference. After completion of this improvement, we tested this improved device repetitively under the various conditions. In conclusion, we identified the generation of the desired contact signal and the prevention of detector failure through plant surveillance test during normal plant operation.

본 논문에서 원전의 핵연료 다발의 중섬자속을 측정할 수 있는 노내중성지속 감시계통의 구동모터를 제어하기 위한 스위치의 오동작 원인 분석 및 이 문제를 해결하기 위한 방안을 제시하고자 한다. 노내중성자속 감시계동은 검출기 안내관을 통해 검출기가 노심으로 삽입되거나 인출될 경우 접점선호를 발생하는 기계식 스위치레버를 장착하고 있다. 그러나 기계적인 열화나 환경적인 요인에 의해 기계식 스위치레버의 특성이 점점 변화되어 마침내 잘못된 접점신호를 발생하게 된다. 그러므로 아들 문제 해결을 위해 기계식 스위지 대선 전자식 스위치를 검출기 안내관 밖에 배치하였고, 공진효과를 이용하여 점점신호를 발생하는 회로개선과 소음 및 전기적 방해를 방지하기 위한 콘데서를 전자회로 전원 입력측에 설치하였다. 이러한 개선을 완료한 후, 여러 조건하에서 이 향상된 스위치 제어회로를 반복적으로 시험하였는데, 결국 이를 통해 원하는 접점신호를 얻게되었을 뿐 아니라 발전소 정상운전 중에 관련시스템의 주기시험을 통해서도 검출기 접점 오동작 신호가 발생되지 않음울 확인할 수 있게 되었다.

Keywords