Mechanical Properties of Insulator FRP Rod According to the Winding Orientation of Glass Fiber

유리섬유의 배향에 따른 전기절연용 FRP의 강도특성

  • 박효열 (한국전기연구소 전략기술연구단) ;
  • 강동필 (한국전기연구소 전략기술연구단) ;
  • 한동희 (한국전기연구소 전략기술연구단) ;
  • 표현동 (부산대 기계설계학과 석사) ;
  • 김태옥 (부산대 재료공학부)
  • Published : 2000.06.01

Abstract

FRP has been used very much as high strength and electrical insulation materials. The fiber contributes the high strength and modulus to the composite. The main roles of the matrix in composite materials like FRP are to transmit and distribute stresses among the individual fibers. The fiber orientation in FRP has a great effect on the strength of FRP because the strength of FRP mainly depends on the strength of fiber. In this study, compressive and bending stresses of FRP rods were simulated and measured according to the winding orientation of glass fiber. Inner part of FRP was made unidirectionally by pultrusion method and outer part of FRP was made by filament winding method to give fiber orientation to the FRP. The shear stresses had great effect on the strength of FRP although the stress of parallel direction of FRP was much higher. The tendency of compressive and bending strengths with glass fiber orientation was different each other.

Keywords

References

  1. D.Dumora, D.Feldman, M.Gaudry, 'Mechanical behavior of flexurally stressed composite insulators,' IEEE Transactions on Power Delivery, Vol. 5, No. 2, pp. 1066-1073, April 1990 https://doi.org/10.1109/61.53123
  2. E.A. Cherney, 'Long-term Mechanical life testing of polymeric post insulators for distribution and a comparison to porcelain,' IEEE Transactions on Power Delivery, Vol. 3, No. 3, pp. 1141-1145, July 1988 https://doi.org/10.1109/61.193896
  3. J. Lanteigne, S. Lalonde, C. De Tourreil, 'Optimization of stresses in the end fitting of composite insulators for distribution and transmission lines,' J. Reinforced Plastic and Composites, Vol. 15, pp. 467-478, May 1996
  4. F. Hammer, 'Insulating systems for HVDC power apparatus,' IEEE Transactions on Electrical Insulation, Vol. 27, No. 3, pp. 601-609, June 1992 https://doi.org/10.1109/14.142725
  5. K. Izumi, T. Takahashi, T. Taniguchi, H. Homma, T. Kuroyagi, 'Performance of line post type polymer insulation arm for 154kV,' 10th International Symposium on High Voltage Engineering, Aug. 25-29, 1997
  6. K. Izumi, 'Development of 154kV compact overhead transmission line applying polymer insulation arms,' Indian J. of Power & River valley development, pp. 214-219, 1997
  7. K. J. Bathe, 'Finite element procedures,' Prentice Hall, 1996
  8. ASTM D790-93, 'Standard test methods for flexural Properties of unreinforced plastics and electrical insulating materials,'
  9. ASTM C674-88, 'Standard test methods for flexural Properties of ceramic whiteware materials,'
  10. R. P. Brown, 'Handbook of plastics test methods (3rd edition)', pp. 139-151, Longman Science & Technical, 1988
  11. ASTM D695-91, 'Standard test method for compressive properties of rigid plastics,'
  12. 김창완외 4인, '강도를 고려한 원통형 복합재료 구조물의 최적 설계,' 대한기계학회 논문집(A), 제20권, 제3호, pp. 775-787, 1996
  13. C. Zweben, H. T. Hahn, T. W. Chou, 'Mechanical behavior and properties of composite materials,' Vol. 1, pp. 62-69, Technomic publishing Co., 1989
  14. J. S. T. Looms, 'Insulators for high voltages,' Peter Peregrinus Ltd, pp. 10-13, 1988