The Analysis of Arc-Flow Interaction in the GCB using the Modified FLIC Method and the Arc Model

Modified FLIC법과 아크 모델을 이용한 차단기 내의 아크 유동 해석

  • 신승록 (서울대 전기공학부) ;
  • 김홍규 (서울대 전기공학부 전임과정(수료)) ;
  • 정현교 (서울대 전기공학부)
  • Published : 2000.03.01

Abstract

In this paper, the analysis of the arc-flow in the GCB is presented by using the modified FLIC method and the arc model. The modified FLIC method adopts the upwind scheme and requires short calculation time. The arc model used in this paper treats the arc as a energy source in the energy equation. The energy source is composed of the ohmic heating and the radiation energy transfer. At each step, the movement of electrode is simulated. From the simulation, reasonable results can be obtained.

Keywords

References

  1. G. Bernard, P.Malkin, W. Legros, 'An $SF_6$ Breaker using the autoexpansion principle', IEEE Trans. on Power Delivery, vol. 3, pp. 1739-1744, October 1988 https://doi.org/10.1109/61.193979
  2. P. Scarps, B. Dauby, J.M. Defise, M.Barrault and G. Bernard, '$SF_6$ Auto- expansion Circuit Breaker Design:Numerical and Experimental Investigations of Arc-Gas Interactions', IEEE Trans. on Power Delivery, Vol.7, No.1, January 1992 https://doi.org/10.1109/61.108927
  3. 김홍규 외 2인, 'Modified FLIC법을 이용한 GCB내의 유동 해석프로그램 개발', 98년 초고압 기기 추계심포지엄 논문집, 1998
  4. R.W.Liebermann, J.J. Lowke, 'Radiation Emission Coefficients for Sulfer Hexafluoride Arc Plasma', J. Quant. Spectrosc. Radiat. Transfer. Vol. 16, pp. 253-264, 1976 https://doi.org/10.1016/0022-4073(76)90067-4
  5. R. A. Gentry, R.E. Martin, 'An Eulerian Differencing Method for Unsteady Compressible Flow Problems', J. of Computational Physics, pp. 87-118, 1966 https://doi.org/10.1016/0021-9991(66)90014-3
  6. X.D.Zhang, J.Y.Trepanier, R. Camarero, 'Modeling and Computation of Arc-Flow Interaction in Circuit - Breakers', Comp. Fluid Dyn., Vol. 2, pp. 41-64, 1994 https://doi.org/10.1080/10618569408904483
  7. 신승록, 김홍규, 정현교, 'Modified FLIC법과 아크 모델을 이용한 차단부내 초기 아크 유동 해석', 1999년 대한전기학회 하계학술대회 논문집, 1999. 7
  8. K. Suzuki, H. Ikeda, H. Mizoguchi, Y. Ozaki, S.Yanabu, 'Investigation of Interruption Performance of Newly Developed 300kV 3-Phase-in-one-tank-type GCB and its Application to Reduced Size GIS', IEEE, 1988 WM 228-9 https://doi.org/10.1109/61.19225