Analysis of Induced Voltage on the Gas Pipeline at the Fault in a Underground Power Cables
지중전력케이블에서 고장발생시 인근 가스배관에 유도되는 전압 해석
Abstract
Because of the continuous growth of energy consumption, and also the tendency to site power lines and pipelines along the same routes, the close proximity of high voltage structures and metallic pipelines has become more and more frequent. Moreover, normal steady state and fault currents become higher as electric networks increase in size and power Therefore, there has been and still is a growing concern(safety of people marking contact with pipeline, risk of damage to the pipeline coating, the metal and equipment connected to pipeline, especially cathodic protection system) about possible hazards resulting from the influence of high voltage power system on metallic structures(gas pipeline, oil pipeline and water pipeline etc.). Therefore, we analyze the interference problems when the gas pipeline is buried with power cable in the same submarine tunnel. This paper present the results of the study about interference mechanism, AC corrosion limitation of safety voltage and analysis of induction voltage.
최근 국내에서는 효율적인 공간활용을 위해 해저터널을 이용하여 전력을 공급하는 것이 시도되고 있으며, 해저터널내에 에너지 공급 기간시설물(전력케이블, 가스배관, 송유관, 지역난방배관 등)들이 같이 포설될 수 있으면 공사비 절감의 효과는 엄청날 것이므로 관심도가 높아지고 있다. 따라서 본 논문에서는 세계최초로 몰타르(Mortar)로 충진되어 있는 해저터널에서 전력케이블과 가스배관이 병행할 경우, 유도에 의한 교류부식에 대하여 검토하였으며, 아직 국내에는 유도전압 제한치가 마련되어 있지 않으므로 인