Effects of Water Aggressivity on the Corrosion in Water Distribution Systems

물의 침식성이 수도관 부식에 미치는 영향

  • Published : 1999.01.15

Abstract

This study was conducted to determine the effects of water aggressivity on the corrosion in a recirculating pipe loop systems. As the pH was increased in the range of pH 6.0~8.5, water aggressivity was decreased. Zine and iron concentration of water adjusted by pH were lower than those of tap water and water adjusted by alkalinity and calcium hardness. The major elements of corrosion deposit analyzed by EDS(Energy Dispersion Spectrophotometer) were zinc and calcium. In conclusion, we suggest that in corrosion control practice in the water works industry, increasing the pH of the water can serve as a way of controlling the solubility of metal ions release from water distribution systems.

Keywords