Actual State of Practical Use and Cooling Effect of Evaporative Cooling Systems

증발냉각시스템의 활용실태 및 냉방효과

  • Published : 1999.12.01

Abstract

In order to take a good look at effectiveness of cooling of Fog system and Pad-Fan system, we chose 49 farm households which were installed evaporative cooling system and 2 farm households which were installed Pad-Fan system and Fog system for a test. We execute the test on 29 households out of 49.6 households, which were installed Pad-Fan system, were able to use; however, 6 household out of 9 which were installed Fog system couldn't use it. The main reason was the clogged on nozzle. The cooling efficiency on Pad-Fan system was 77.4%, but it was very poor on Fog system. Since there are many problems on Fog system, we need more research on size of fog, the location of nozzle, control of Fog systems.

현장조사 결과 패드-팬 시스템의 경우 6개 농가 모두 사용하고 있었으며, 온실 내기온은 외부기온보다 2~5$^{\circ}C$ 낮았다. 이시스템의 냉방효율은 평균 77.4% 이었으며, 외부의 상대습도가 60%이하 일 경우 냉방 효율이 높았다. 포그 시스템의 경우 현장조사에서 9농가 중 6농가가 사용을 못할 정도로 많은 문제점이 발견되었다. 포그입경, 분무수량, 운영 방법등 개선해야 할 사항이 많았다. 실험온실의 경우도 노즐의 설치 위치와 제어방법에서 문제점이 발견되었다. 포그입자가 커 증발하지 못하고 대부분이 바닥과 차광망으로 낙하하였고, 지역 기상조건을 고려하지 못한 제어방법으로 냉방효과를 떨어뜨리고 있었다. 냉방효과를 높이가 위하여 노즐의 위치 선정, 제어방법에 대한 연구가 수행되어야 하며, 지역적 기상특성을 고려한 연구와 내부 습도를 낮게 유지하는 연구도 수행되어야 할 것이다.

Keywords