Abstract
This paper describes the cycle performance of heat-pump system using R-22 and R-290. Experiments were performed in the smooth tube with inside diameter of 10.07mm and outside diameter of 12.07 mm and grooved inner tube having 75 fins with a height of 0.25mm Condensing temperatures were held constantly between 318K and 328 K while evaporating temperatures were varied from 257 K to 288 K mass velocities from 51 to $280 kg/m^2s$. From the experiments it was known that the evaporating temperature and condensing temperature had more affected by the compressor shaft power than the tube geometries. Cooling capacity of the R-22 and R-290 had similar values in the smooth and grooved inner tubes. The coefficient of performance(COP) was calculated using the compressor shaft power volumetric refrigeration capacity compression ratio and cooling capacity. The COP of the R-290 had slightly higher values than that of R-22 The major parameters affecting the heat pump cycle performance wee the refrigerant proper-ties and operating conditions rather than the geometric shapes of the heat exchanger