Ondol Heating System Using Heat Pump - Comparison of Energy Consumption between the Heat Pump and the Oil Boiler -

열펌프를 이용한 온돌 난방 시스템 - 열펌프와 석유보일러의 소요에너지 비교 -

  • 김현철 (충북대학교 농과대학 농업기계공학과) ;
  • 송현갑 (충북대학교 농과대학 농업기계공학과)
  • Published : 1999.08.01

Abstract

In these days, we are faced to a couple of difficult problems, the one is the unstable price of the energy due to the shortage of fossil fuel resources and the other is the serious environmental pollution from the excessive consumption of fossil fuel. In order to save the thermal energy for the house heating, in this study the heat pump using the natural thermal energy resources was provided for Ondol heating and the thermal energy consumption of the heat was compared to that of oil boiler. The results could be summarized as follows: 1. In the Ondol room the temperature difference between the Ondol surface and room air was about 5∼$10^{\circ}C$ in accordance with the ambient temperature. 2. The Ondol room heating efficiency of the heat pump with compressor of 2PS was the highest at the water flow rate of 200 l/h. 3. The energy saving rate of the heat pump to the oil boiler for heating the Ondol system was 19.3%. 4. The Ondol heating cost of the heat pump was less 20.6% than that of oil boiler when oil price was 478 won/l.