A Study on Diagnosis of The Energized Status of 22.9kV Multigrounded Underground Power Cable

22.9kV 다중 접지 지중 전력 케이블의 가압 상태 진단에 관한 기초 연구

  • Published : 1999.10.01

Abstract

An experimental study to identify the energized status of the 22.9kV underground power cable by the detection of vibration has been performed. We have derived that there exists vibration at double the line frequency in live cables by electromagnetic force. The relative amplitudes of the cable vibration according to the energized status of the cable were calculated by computer simulation. The cable vibration can also be picked up by accelerometer. A prototype was tested on the underground distribution system in Chonan substation, KEPCO. Comparison between simulation results and field test results was performed. The results showed that the energized status of the calble can be identified by measuring the vibration of the cable using accelerometer.

Keywords

References

  1. Underground Power Transmission P. Graneau
  2. Underground Systems Reference Book Edison Electric Institute
  3. Transmission & Distribution Shielded Cable is Tested to Determine if it is Energized T. D. Walsh;T. M. Feldman
  4. United States Patents Number 5397983 Zivan Zarbar;Bernard R. S. Cheo
  5. Electromagnetic Wave and Radiating Systems(2nd Ed.) E. C. Jordan;K. G. Balmain
  6. Piezoelectric Accelerometer and Vibration Preamplifier Handbook Mark Serridga;Torben R. Licht