초록
Corona discharges form at the surface of a transmission line conductor when the electric-field intensity on the conductor surface exceeds the breakdown strength of air. In order to decrease the electric-field intensity on the conductor surface, a new 6 conductor bundle has been studied. This bundle, hybrid conductor bundle, consists of using a larger subconductor at the bottom two conductor positions in the 6-conductor bundles of each phase of the line. The electric field on these two larger subconductors is reduced which in turn reduces the corona noise. It is shown that this is a better solution for decreasing the electric-field intensity than ether the conventional bundle or the asymmetric bundle proposed by EPRI.