고압한류퓨즈의 최적 차단을 위한 설계변수의 영향

The Effects of Design Parameter to Interrupt Optimally for High Voltage CL Fuse

  • 이세현 (대전기능대 전기기술학과) ;
  • 한상옥 (충남대 공대 전기공학과)
  • 발행 : 1999.03.01

초록

The fuse used in the high voltage distribution line often fails due to the active ionization caused by the strong electric field at fuse terminal. To suppress the ionization at the high voltage and high capacity current limiting fuse, the particle size and compactness of silica sand, the design, length, notch number and material of element, the diameter and length of fuse body must be considered carefully. However, these are not many proper which is treated with the inherent interrupting characteristics from many parameters at present. Because of these reasons, time and effort are needed to develop the new type fuse by the fuse designers in relation with the inherent characteristics from each of parameters. In this paper we choose 7 parameters with weight value based on study and experimentation and analyzed the characteristics of arcing period. In addition, we proposed the experimental method to experimentation and analyzed the characteristics of arcing period. In addition, we proposed the experimental method to extract the optimal design parameters with minimal effort as related the mutual effect from each of the parameters.

키워드

참고문헌

  1. Korean-Japan Joint Symposium on Electrical Discharge and High Voltage Engineering Element Shapes on High-Rupturing-Capacity Fuses Lee Sei-Hyun;Park Doo-Kee;Koo Kyung-Wan;Han Sang-Ok
  2. Elektoekhnika [Soviet Electrrical Engineering] no.9 Effect of Design Features of the Fusible Element of Fuses on the Arc Pocesses in Them K.K. Namitokov;Z.M. Frenkel
  3. IEEE Transactions on industry applications v.30 no.1 Design Development And Application Of Smart Fuses Part 1 Radhakrishanan Ranjan
  4. J .Phys. D: Appl. phys. v.26 Dynamics of Fulgurite Formation During Arcing in hrc Fuses K. Jakubiuk;T. Lipski
  5. Int. Conf. on Electric Fuse and Their Applications Arc Energy and Critical Tests for HV Current Limiting Fuses V. N. Narancic; G. fecteau.
  6. 대한전기학회 논문지 v.46 no.8 한류퓨즈의 단락시험을 위한 등가 차단기와 단락발전기의 특성 시뮬레이션 이세현;한상옥
  7. 대한전기학회 논문지 v.46 no.4 특고압한류퓨즈의 차단특성 모델링 이세현;한상옥