Environmental Impact on the KEPCO 765-kV Double Circuit Transmission Line

한전 765 kV 2회선 송전선로의 전기환경장애 특성

  • Lee, D.I (Technology Development Center, Korea Electric Power Research Institute) ;
  • Sin, K.Y (Technology Development Center, Korea Electric Power Research Institute) ;
  • Kim, J.B (Technology Development Center, Korea Electric Power Research Institute)
  • 이동일 (한전전력연구원 전력계통연구실 송변전기술그룹) ;
  • 신구용 (한전전력연구원 전력계통연구실 송변전기술그룹) ;
  • 김정부 (한전전력연구원 전력계통연구실)
  • Published : 1999.02.01

Abstract

The environmental impact of the KEPCO 765-kV transmission line was studied using a full scale test line in order to develop the design technology. Therefore this paper describes an environmental design summary of the audible noise, hum noise, wind noise, radio interference, TV interference and electric field measurement from the KEPRI 765-kV double circuit transmission test line with a bundle of $6-480mm^2$ conductors per phase. The analysis of the test results shows that 6-Rail and 6-Cardinal conductors bundle satisfy the audible noise criterion & TV interference under the stable rainy weather condition and the radio interference level under the fair weather. And the other items are also agreed with the design level criterion for KEPCO 765-kV transmission line.

Keywords

References

  1. 96 SM 461-4 PWRD,IEEE Transactions on Power Delivery v.12 no.3 Audible Noise Performance of 6-Rail Conductors on a 765-㎸ Double Circuit Test Line D. I. Lee;J. B. Kim;Kwang, Y. Shin;K. H. Yang;H.S. Ahan;J. Y. Koo
  2. ANSI/IEEE Standard 656-1992 IEEE Standard for the Measurement of Audible Noise from Overhead Transmission Lines
  3. CIGRE v.36-5 AKAGI 1000㎸ project in CRIEPI Corona Test Facilities and Results up to 1983 Y. Sawada;M. Fukushima;M. Yasui
  4. KSA0701-1987 The method of sound level measurement Korea Standard
  5. JIS Z8731-1983 The method of sound level measurement Japan Industrial Standard
  6. IEEE Transactions on Power Apparatus and Systems v.PAS-100 no.1 Formulas for Predicting Audible Noise From Overhead High Voltage AC and DC Line V. L. Chartier;R. D. Stearns
  7. Canadian Communication & EHV Conference Montreal;IEEE CAT. No. 72 CHO 698-1-REG 7 A Semi-Empirical Formula for Evaluation of Audible Noise from Line Corona N. Giao Trinh;P. Sarma Maruvada
  8. Transmission Line Reference Book - 345㎸ and Above(Second Edition)
  9. IEEE Transactions on Power Apparatus and systems v.PAS101 no.10 A Comparison of Methods for Calculating Audible Noise of High Voltage Transmission Lines A report prepared by a Task Force of the Corona and Field Effects Subcommittee
  10. AIEE Transactions, pt. Ⅲ(Power Apparatus and Systems) Radio Interference Studies for Extra-High-Voltage Lines in Ontario J. REICHMAN;J. R. LESLIE
  11. Report of Akagi UHV test line CRIEPI
  12. Electrical Design Handbook for AC Overhead Transmission Lines from 187㎸ to 1,100㎸ CRIEPI