Adaptability of Evaporative Cooling System for Greenhouses to the Weather Conditions of Korea

증발냉각시스템의 온실냉방 적용성 평가

  • Published : 1998.12.01

Abstract

The adaptability of an evaporative cooling system to hot summer climate in greenhouses was comprehensively judged by fuzzy theory, based on the 20 years(1975~1994) weather data of nine representative regions in Korea. As uses the evaporative cooling system for greenhouses during summer in Korea, the inside air temperature of most regions except the southwest coastal areas, the south coastal areas, and Cheju island can be basically controlled below 32.5$^{\circ}C$, and ventilating air can be cooled 5$^{\circ}C$ and more. The analyzed results in this paper are on the basis of good ventilation system. When the evaporative cooling system is applied, the ventilation system which has good air flow organization is needed. Although the summer climate in Korea is high temperature and humidity, evaporative cooling systems are suitable for farm buildings in most regions. This facts better meet the needs of cooling for greenhouse in summer and provides a scientific basis for spreading the evaporative cooling system It is proposed that the further research is needed about the application of evaporative cooling system to greenhouses.

우리 나라의 기후구분에 따른 대표적인 9개 지역의 20년간(1975~1994) 기상자료를 기초로 여름철 고온기(6, 7, 8월) 온실에 대한 증발냉각시스템의 적용성을 퍼지이론에 의하여 종합적으로 평가해 보았다. 남부서해안과 남해안, 제주도 등 일부지역을 제외한 대부분 지역에서 증발냉각시스템을 이용하여 온실의 실내온도를 32.5$^{\circ}C$ 이내로 제어하는 것이 가능하며, 증발냉각시스템에서의 냉각범위가 5$^{\circ}C$이상으로 나타났다. 본 논문에서 분석한 결과는 환기시스템이 잘 갖추어진 것을 전제로 하였으므로 증발냉각시스템을 적용할 경우에는 충분한 기계환기시스템을 갖출 필요가 있다. 우리 나라의 여름철 기후는 고온다습하지만 증발냉각시스템의 적용성은 충분히 큰 것으로 판단되므로 확대보급을 위한 기술의 체계화 연구가 지속적으로 이루어져야 할 것으로 판단된다.