An analysis of fluid flow In U-bend area of laminated plate heat exchanger

적층형 판 열교환기의 U턴부 유동해석

  • 이관수 (한양대학교 기계공학부) ;
  • 박철균 (한양대학교 대학원 기계공학) ;
  • 정지완 (한양대학교 대학원 기계공학과)
  • Published : 1998.05.01

Abstract

The flow characteristics inside U-bend tube of the laminated plate heat exchanger were numerically investigated. The behavior of fluid flow, and the variations of the faulty area and friction factor are examined according to the distance between the span and the wall and the diameter of the round attacked to the end of span. The results show that the diameter(d) of the round attached to the span is mainly associated with the smooth circulation of fluid flow rather than the size of faulty area and the friction factor. As the distance($\ell$) between the span and the wall decreases, the faulty area decreases, however the friction factor dramatically increases. It is also found that one can obtain a good result in the view of the flow characteristics and pressure drop at d=7.5mm and $\ell$=30.5mm.

Keywords