Prediction of Nucleate Pool Boiling Heat Transfer Coefficients of Ternary Refrigerant R407C

  • Kwak, Kyung-Min (Dept. of Mechanical Eng., Yeungnam University) ;
  • Bai, Cheol-Ho (Dept. of Mechanical Eng., Yeungnam University) ;
  • Chung, Mo (Dept. of Mechanical Eng., Yeungnam University)
  • Published : 1998.08.01

Abstract

The nucleate boiling heat transfer experiments are performed using a ternary refrigerant R407C which is a candidate of alternatives of HCFC 22. The boiling phenomena of R-32, R-125 and R-134a which are the constituent refrigerants of R407C are also investigated. The nucleate boiling heat transfer coefficients of R407C are less than those of HCFC 22 which have the similar physical and transport properties. In our experimental pressure range, which is similar to the operational pressure of air conditioning system, the deterioration of boiling heat transfer coefficients of mixture refrigerant R407C does not appear for moderate wall superheat region. Since nucleate boiling heat transfer coefficients cannot be obtained from ideal mixing law of mixture, Thome's method was used to predict. To account for the heat flux effect and system pressure in Thome's method, the correcting factor, a(P.L1T), was introduced and obtained from experiments for ternary refrigerant R407C.

Keywords