Abstract
The influence due to particle contaminated on spacer surface is remarkable in the decreasing of dielectric strength in SF6 GIS. In relation with this problem, We studied, AC flash-over voltage characteristics and breakdown mechanism are investigated under metallic and insulating particle initiated condition in SF6 gas by varying the particle position, particle shape with a plane-plane electrode. The main results are as follows $\circled1$ Influence of the flash-over voltage decrease for particle position is lowest in mid gap and is highest in separated small gap on electrode. $\circled2$ The metallic particle shape which results in the more reduced flash-over voltage, the FOV saturation moved in to the region of low pressure. $\circled3$Insulating particle less than 0.6[mm] are not almost influenced by the flash-over Voltage.oltage.
스페이서 표면 파티클에 의한 오염의 영향은 SF6GIS의 절연내력을 현저히 감소시킨다. 이와 관련해서 우리는 평행평판전극 구성으로 SF6가스중에서 금속 및 비금속 파티클의 위치 및 형태를 변화시키면서 교류전압에서 섬락전압 특성과 파괴 기구에 대해서 연구했다. 주된 결과는 $\circled1$파티클 위치에 대한 섬락전압 감소의 영향은 갭중간에서 가장 적고 전극에서 미소간극 분리된 경우의 영향이 가장 커다. $\circled2$ 섬락전압 감소가 크게 되는 금속 파티클 일수록 FOV 포화 현상은 낮은 압력 영역으로 이동된다. $\circled3$0.6[mm]이하의 비금속 파타클은 섬락전압에 그의 영향을 미치지 않는다.