참고문헌
- Fluid mechanics(3th Edition) Frank M. White
- ASHRAE HANDBOOK Refri-geration System and Applications ASHRAE
- 냉동설비공학 윤정인(외)
- 第30回空氣調和 · 冷凍聯合講渡會講渡論文集 HFC冷媒 · 冷凍サイクルシミュレツョン 池元眞佐美;山本泰司;黑河通屋;名道賢二;片罔久典
- 冷凍空調便覽 v.2 日本冷凍會
The purpose of this study is analyzing the performance of sea water cooling system under various refrigerant pipe length. In sea water cooling system, the increase of refrigerant pipe length cause increases of pressure drops. These pressure drops cause fresh gas in liquid pipe and increase specific volume in gas pipe outlet, so sea water cooling system capacity is decreased by decrease of refrigerant mass flow rate. Sea water cooling system capacity in refrigerant pipe length 70m is decreased more than 30% when compared with pipe length 10m and the decrease of the coefficient of performance is nearly 20%.