Abstract
The first purpose of this study is to verify the application of computer modelling to a enclosed space fire. The second one is to determine temperature distribution for the three different ventilation types in case of a enclosed space fire. The third one is to find out the ventilation direction and ventilation quantity to remove effectively heat and combustion products generated by a fire in variable air volume(VAV) system. Firstly, compared with experimental results of Lawrence Livermore National Laboratory(LLNL), numerical results show good agreements. Secondly, among three different ventilation types, the numerical analyses show the highest temperature distribution in occupied zone(up to 1.8 m from bottom) from firing moment to 100 sec. when supply ducts are placed in ceiling and extract duct is placed close to the bottom on side walls. This is due to disadvantageous position of extract duct in ventilating high temperature air which rise because of buoyancy force. Thirdly, this study finds out effective ventilation direction and ventilation quantity to remove heat and combustion products generated by a fire by using VAV system. $CO_2$ concentration is used as a fire fume removal index. As soon as a fire happens, ventilation direction is changed in order to gather and drive out fire fumes. In case of three times ventilation quantity of ordinary one, $CO_2$ concentration and temperature have begun to decrease at 120 sec. after firing, i.e.fire fumes have begun to be removed.