A study on the energy efficient operation of economizer cycle control
외기냉방제어의 효율적인 운영에 관한 연구
Abstract
As the cooling energy requirement in an office building increases due to the increased internal heat gains, the effort to minimize the energy consumption through efficient operation of existing HVAC systems will be beneficial. In this study, one of the energy conserving efforts in an office building, operational strategies of Economizer Cycle Control have been investigated through DOE-2.1E computer simulation. The findings can be summarized : 1) Economizer Cycle Control saves energy throughout the year, 2) Econo-Limit-T must be applied seasonally based on the outside and return air conditions, 3) use of Enthalpy control is more energy efficient than that of Temperature control.
Keywords