An experimental study on the multiple parameter switching control for floor heating system

바닥 난방공간의 다인자 제어에 관한 실험적 연구

  • 조성환 (한국에너지기술연구소 건물에너지연구부) ;
  • 태춘섭 (한국에너지기술연구소 건물에너지연구부) ;
  • 장철용 (한국에너지기술연구소 건물에너지연구부)
  • Published : 1997.11.01

Abstract

An experimental facility consisting of two $3{\times}4.4{\times}3.8m$ rooms identical in construction is built. Each room has a control system and storage tank supplying hot water to the radiant floor heating system. The facility enables simultaneous comparision of two different control stratigies each implemented in a separate room. The operating performance of three kinds of flow control scheme is tested and compared in this study : (i) conventional on-off control based on feedback from room air temperature (ii) TPSC(two parameter switching control) (iii) TPOC(two parameter on-off control). Results show that TPSC and TPOC using room air and surface temperature sequentially as feedback signal to control hot water supply is the better temperature regulation scheme than conventional control based on feedback from only room air temperature. They are good candidates for the room with radiant floor heating system under continuous and intermittent heating mode.

Keywords