Design and performance analysis of water-to-air heat pump system using double-tube heat exchanger

이중관 열교환기를 사용한 물 대 공기 열펌프 시스템의 설계와 성능해석

  • 한도영 (국민대학교 기계.자동차공학부) ;
  • 박관준 (국민대학교 대학원 기계공학과)
  • Published : 1997.11.01

Abstract

The water-to-air heat pump system requires relatively lower energy consumption and less installation space. The heat exchangers used for this system are the finned-tube type for the indoor unit and the double-tube type for the outdoor unit. Mathematical models for this system are developed and programmed in computer. Experimental data from various conditions are obtained and compared with calculated values from the computer simulation program. Differences of cooling capacity and COP are 1.25% and 0.47%, and those of heating capacity and COP are 0.51% and 0.13%, respectively. Simulation results are in good agreement with test results. Therefore, the developed program is effectively used for the design and the performance prediction of water-to-air heat pump system.