Characteristics of Heat Transfer in a Heat pipe Controlled by Solenoid Valve

전자 밸브에 의해서 제어되는 히트파이프의 전열 특성

  • Published : 1997.03.31

Abstract

The purpose of this research is the study of characteristics of heat transfer in a heat pipe controlled by solenoid valve. A solenoid valve located to the adiabatic section between evaporator and condenser of heat pipe was used to control the valve action for effective energy transfer of the industrial exchanger machine. By the results presented in this study temperature difference between evaporator and condenser increases with increasing the temperature frequency and with decreasing the temperature amplitude. When inclination angle and flow rate of cooling water increases, the temperature amplitude is reached to the steady state rapidly with increasing the temperature frequncy.

본 연구에서는 히트파이프의 제어를 전자밸브에 의하여 단속 되어질 때 증발부의 상태변화가 응축부에 미치는 전열제어 특성을 연구한 것이다. 증발부와 응축부사이의 단열부에 전자밸브를 설치하여 증발부의 열저장에 따른 밸브제어의 영향, 밸브주기 개폐에 따른 응축부의 응답특성, 경사도, 입열량, 냉각수량변화가 전열에 미치는 연구를 실행하고 증발부와 응축부의 유동특성을 고찰하여 전자제어밸브에 따라 증기의 동특성영향을 연구한다. 그 결과는 응축부와 증발부사이의 온도차가 크면 온도의 진동수는 증가하고, 온도의 진폭은 감소한다. 제어밸브의 개폐시간이 지연되면 증발부의 펄스비등은 강하게되고 밸브개폐후 응축부의 온도 진동은 지연 감쇄한다.

Keywords