A Study on the Heat Flow Characteristics and High Efficiency Thermal Storage of Inflowing Warm Air in the Room

실내유입온기의 열유동특성과 고효율 축열에 관한 연구

  • Published : 1997.06.30

Abstract

A study on the distribution characteristics of inflowed warm air is important to analyze warm air storage in a room. Also, in point of energy saving during heating, warm air flow characteristics occurred by circulation and distribution of inflowed warm air should be analyzed, and the storage efficiency should be considered in order to increase efficiency of heating system. For this study, in the real-sized model room, the temperature differences between inflowing warm air and inner room air are 10, 20, $30^{\circ}C$(3steps), and the flow rates of inflowing warm air are 0.5, 1, 2, 3m/s(4steps) respectively as dynamic parameters. Also, anemos and vane diffuser are used as inlet geometric condition. Consequently, on geometric conditions, high thermal storage efficiency can be obtained with the vane diffuser, and heat flow characteristics depend on the inflowing velocity more than reference temperature difference.

본 연구에서는 실내로 유입되는 온기와 실내공기사이의 온도차 및 유입속도에 따라 발생되는 부력의 영향 및 실내로 유입된 온기의 혼합특성에 관한 열유동특성을 파악하였다. 혼합도의 정의로부터 임계속도($1.2{\sim}1.6m/s$)전 후로 기하학적영향에 대하여서 혼합과의 관계를 파악할 수 있었다. 그리고 축열표율과의 관계는 속도가 크고 기준온도차가 작을수록 부력의 영향을 적게 받아서 아네모스형, 베인형 모두 높은 축열효율을 나타냈다. 그리고 속도가 클 때는 베인형이 전반적으로 우수한 축열효율을 나타냈다. 따라서 유입속도에 의한 영향이 기준온도차에 의한 영향보다 지배적임을 알 수 있었다.