도로터널 조명시설의 설계기준

  • Published : 1997.02.01

Abstract

In this paper, the results of the measurement and analysis of extremely low frequency(ELF) electric field in the vicinity of 154[kV] overhead transmission lines have been described. The planar-type electric field sensor has been fabricated by three dimensional structure with special consideration of taking the power frequency and lower components. The calibration experiments have been carried out according to the procedures of IEEE recommendation. The electric field measuring system has the frequency bandwidth of 7[Hz] to 2.7[MHz] and the response sensitivity of 0.094[mV/V/m]. Also the practical measurements of electric field under an 154[kV] double circuit overhead transmission lines have been made and analyzed. It was known that the lateral electric field profiles under an 154[kV] double circuit overhead transmission lines show the asymmetrical distributions owing to the environmental metal frame structures and their maximum electric field magnitude is less than 3[kV/m]. It can be concluded that the measured results of the electric fields satisfy with all limits or guidelines of the various authorized international institutes' recommendations.

본 논문에서는 154[㎸] 가공송전손로의 주변에서 발생하는 극저주파 영역(ELF)의 전장의 측정 분석한 결과에 대해서 기술하였다. 상용주파수와 같은 저주파 성분의 검출을 위한 3차원 평행평판형 전장센서를 제작하였으며, IEEE에서 추천하는 실험방법을 적용하여 교정실험을 수행한 바 제작된 전계측정장치의 주파수 대역은 7[Hz]에서 2.7[MHz]이고, 응답 감도는 0.094[mV/V/m]이었다. 154[㎸] 2회선 가공송전선로 아래에서 전장의 실측 실험을 수행하고, 그 결과를 분석하였다, 가공송전선 아래에서의 전장의 분포는 주변의 금속 물체 때문에 비대칭 형상을 나타내었으며 그리고 최대 전계의 세기는 3[㎸/m]이하이었다. 본 연구에서는 측정 결과는 관련 여러 국제기관의 제한 권고치를 만족시키고 있다.