DOI QR코드

DOI QR Code

Natural convection cooling of discrete heaters with same heat generation in a vertical open top cavity

상부가 개방된 수직 캐비티내에 장착된 불연속 균일 발열체의 자연대류 냉각

  • 유갑종 (경북대학교 공과대학 기계공학과) ;
  • 추홍록 (대구보건전문대) ;
  • 김병하 (경북산업대학교 기계설계과) ;
  • 최병철 (경북대학교 대학원 기계공학과)
  • Published : 1997.01.01

Abstract

Natural convection cooling of discrete heaters located in a two-dimensional vertical open top cavity is investigated experimentally. The five discrete heaters with same heat generation are located on the wall of the cavity. The heaters are arranged in two configurations; flush-mounted on a vertical wall and protruding from the wall about 4.5 mm. The materials used for the vertical walls are copper and epoxy-resin, and air is used as the cooling fluid. The temperature and flow fields in the cavity were visualized by means of Mach-Zehnder interferometer and smoke-method. Also, local temperature measurements are made along the vertical wall. Results are obtained for cavity aspect ratios of 4.6, 7.5 and 9.5 and modified Rayleigh numbers ranging from 10$^{3}$ to 10$^{6}$ . Results indicate that the cooling efficiency for the copper wall is superior to that of the epoxy-resin. For the epoxy-resin wall, the protrusion of the heaters plays a role in decreasing the heat transfer performance. The location of maximum temperature is significantly influenced by the wall materials and heater configurations. Correlations relating the Nusselt number to the modified Rayleigh number are proposed.

Keywords