A Study on the Thermodynamic Performance of Plastic Bottle Ice Storage System

플라스틱병을 이용한 빙축시스템의 열역학적 성능에 관한 연구

  • Published : 1996.11.01

Abstract

This paper presents an anlaysis on the thermodynamic performance of ice storage system. The primary interest in this work is the exergetic efficiency of the system. The ice storage system considered here is the capsule type system with the waste plastic bottle being used as a capsule. To examine the characteristics of irreversibility production and exergetic efficiency in detail the ice storage system to be analyzed has been separated from the refrigerator in this analysis. The analysis is based on the lumped model with 3 uniform temperatures. The results indicate that 3 dimensionless parameters can describe the exergetic efficiency of the system, from which the characteristics of irreversibilities and the ranges of these parameters to ensure the reasonable performance of the system can be found. Experiments also have been performed to demonstrate the feasibility of such a system. This analysis only shows the performance of ice storage side, with the refrigeration side excluded. However, the results can be interpreted as a total performance if the refrigerator coupled with the ice storage system operatres reversibly.

Keywords

Acknowledgement

Supported by : 한국학술진흥재단