Fourteen(14) large commercial buildings located in Seoul with friable sprayed-on surface insulation material on ceiling were investigated for fiber types in bulk material and for airborne fiber concentrations in buildings by transmission electron microscopy (TEM) in order to compare the results with those by polarized light microscopy (PLM) and phase contrast microscopy (PCM). The results were as follows: 1. Chrysotile asbestos was found in one bulk sample out of total 14 bulk samples collected. Glass fiber and mineral wool were the two major constituents of the bulk samples. 2. The Na-Mg-Si-Ca-Fe-Al ratios of the EDX spectra which were normalized with the Si peak were 0-1.0-10-8.3-4.0-4.0 in mineral wool and 0-5-10-21-0-0 in chrysotile asbestos, respectively. 3. Airborne fiber concentrations were log-normalcy distributed and the geometric mean (geometric standard deviation) fiber concentrations by TEM in the underground parking lots and inside buildings were 0.0048 f/cc(1.93) and 0.0040 f/cc(2.27), respectively with no statistical difference. In the outdoor ambient air, statistically significantly lower concentration of 0.0018 f/cc(2.04) was measured. 4. The TEM/PCM ratios of airborne fiber concentrations ranged 0.5 - 2.0 for 80 % of airborne samples analyzed, end the regression equation between TEM and PCM was PCM=-0.2724+1.1355(TEM) with the coefficient of determination