Abstract
This study was to estimate how about various effects on the body thermal sensation as air velocity. clo. mean radiant temperature and resultant temperature are varied. The indoor thermal environment elements are measured under the five different of air velocity. Using the above considerations. the following results are obtained. ▶ The states, the air velocity under 0.5 m/s and 0.63 to 0.9 clo. were shown that the comfort zone of mean radiant temperature by 21.2~24.7C, the neutral point by 22.8C, the resultant temperature by 20.7-24.4C and the neutral point by 22.6C. ▶ On equal condition, the draft was occurred at a given air-velocity under 0.5m.s. It was also appeared the floor panel heating system affecting the body thermal sensation by the subject’s below-chest parts and the local discomfort by sensations on the feet and the knees.