A study on the comfort thermal environment by the Draft in floor panel heating system

바닥면복사난방에서 Draft에 의한 쾌적열환경에 관한 연구

  • Published : 1996.07.01

Abstract

This study was to estimate how about various effects on the body thermal sensation as air velocity. clo. mean radiant temperature and resultant temperature are varied. The indoor thermal environment elements are measured under the five different of air velocity. Using the above considerations. the following results are obtained. ▶ The states, the air velocity under 0.5 m/s and 0.63 to 0.9 clo. were shown that the comfort zone of mean radiant temperature by 21.2~24.7C, the neutral point by 22.8C, the resultant temperature by 20.7-24.4C and the neutral point by 22.6C. ▶ On equal condition, the draft was occurred at a given air-velocity under 0.5m.s. It was also appeared the floor panel heating system affecting the body thermal sensation by the subject’s below-chest parts and the local discomfort by sensations on the feet and the knees.

Keywords

References

  1. 실내온도 환경 평가 지표 명 현국
  2. 공기조화설비 신치웅
  3. 건축환경계획 이경희
  4. Thermal Comfort P. O. Fanger
  5. ASHVE Research Report No. 1362 - Air distribution and draft (ASHVE Trans.) v.55 J. Rydberg;Norback
  6. ASHRAE Trans. v.91 A New Simpler Method for Estimating the Thermal Insulation of an Ensemble Olesen, B. W.
  7. International Standard ISO 7730 Moderate T-hermal Environment Determination of the PMV and PPD Indices and Specification of the Conditions for Thermal Comfort
  8. ASHRAE, ASHRAE 55-1992 Thermal Environmental Conditions for Human Occupancy
  9. ASHRAE Trans v.78 Future Research Needs Concerning The Human Response To Indoor Environment P. OLEFANGER
  10. Theorie Simplifie du Thermometre Resultant, chauffageet Ventilation Missenard, A.
  11. 啓明大學校 博士學位 論文 集合佳沃의 熱環境에 관한 硏究 한윤호
  12. 嶺南大學校 博士學位論文 低溫床面輻射煖房의 坐式生活時 接觸에 의한 局部的 不滿足 硏究 윤형수