대형발전기 고정자권선 절연재료의 열 사이클에 의한 열화에 관한 연구

A study on the heat cycle aging of insulation materials in large generator stator windings

  • 김희곤 (한전 전력연구원 수화력 발전연구실) ;
  • 박영관 (성균관대 공대 전기공학과)
  • 발행 : 1996.04.01

초록

Heat cycle aging of insulating materials in large generator stator winding has been investigated using both on-line and off-line test methods. On this study, principally, off-line test against actual generator in service was carried out to acquire information about polarization index(PI) and dissipation factor, dissipation factor tip-up, maximum partial discharge for the purpose of remnant breakdown voltage and life assessment. It was found from the tests that both dissipation factor and maximum partial discharge decreased with the increase of operating hours and starting numbers. It was found from off-line tests that the remnant breakdown voltage had a strong relationship with both dissipation factor and maximum partial discharge the remnant breakdown voltage as a results of both operating hours and starting number and the nondestructive tests were proposed as parameters which can predict the remnant lifetime of insulating materials in large generator stator windings. (author). 8 refs., 8 figs., 2 tabs.

키워드