On-line partial discharge measurement techniques of hydro-generator windings
수력 발전기 권선에서의 운전중 부분방전 측정기법
Abstract
In hydro-generator, a groundwall insulation of stator windings gradually deteriorates due to mechanical, thermal, electrical and environmental stresses. These stresses combine to result in loose windings, delamination of the stator insulation and/or electrical tracking of the endwinding, all of which can lead to stator insulation failures. Conventionally, off-line tests such as partial discharge measurement, DC/AC current and .DELTA.tan.delta. tests has been used for estimation of winding condition. However, off-line test requires large power supply and generator outage. In addition, major cause of insulation problems such as loose wedges and slot dischages may not be found with off-line diagnoses. This paper introduces the on-line partial discharge measurement techniques using frequency spectrum analyzer(FSA) for the generator stator windings. The experimental results from the UIAM #1 hydro-generator confirms a optimistic application of on-line generator diagnosis method as a reliable tool for evaluation of winding condition.
Keywords
- Hydro-Generator Stator Winding;
- Partial Discharge(PD);
- On/Off-Line Insulation Diagnosis;
- Partial Discharge Analyzer(PDA);
- Frequency Spectrum Analyzer(FSA)