On-line partial discharge measurement techniques of hydro-generator windings

수력 발전기 권선에서의 운전중 부분방전 측정기법

  • 황동하 (한국전기연구소 발전기 진단연구팀) ;
  • 김진봉 (한국전기연구소 발전기 진단연구팀) ;
  • 김용주 (한국전기연구소 발전기 진단연구팀) ;
  • 박명수 (한국전려공사 전력연구원) ;
  • 김택수 (한국전려공사 전력연구원)
  • Published : 1996.02.01

Abstract

In hydro-generator, a groundwall insulation of stator windings gradually deteriorates due to mechanical, thermal, electrical and environmental stresses. These stresses combine to result in loose windings, delamination of the stator insulation and/or electrical tracking of the endwinding, all of which can lead to stator insulation failures. Conventionally, off-line tests such as partial discharge measurement, DC/AC current and .DELTA.tan.delta. tests has been used for estimation of winding condition. However, off-line test requires large power supply and generator outage. In addition, major cause of insulation problems such as loose wedges and slot dischages may not be found with off-line diagnoses. This paper introduces the on-line partial discharge measurement techniques using frequency spectrum analyzer(FSA) for the generator stator windings. The experimental results from the UIAM #1 hydro-generator confirms a optimistic application of on-line generator diagnosis method as a reliable tool for evaluation of winding condition.