Abstract
An effective heat transfer during freezing process was proposed in the vertical cylinder to improve the effectiveness of the heat storage. Vertical cylinder was filled with pure water in order to investigate ice-shape, temperature distribution of the liquid, temperature distribution of the cylinder tube wall, total heat storage per unit mass in the test section under the two experimental conditions; inlet temperature of working fluid is constant($-10^{\circ}C$) and inlet direction of working fluid is either upward flow or downward. Both the mean temperature of the liquid and temperature difference of cylinder tube wall in the upward were lower than those in the downward. In case that the initial temperature of water was $7^{\circ}C$ and $4^{\circ}C$, the shape of ice layer in the upward was more uniform than that in the downward. In case of $1^{\circ}C$, the shape of ice layer is formed by inlet direction of working fluid. Finally, time-varying total heat energy stored in the water in the upward was higher than that in the downward.
본 연구는 용융점 온도가 $0^{\circ}C$인 순수 물이 수직원통형 빙축열조 내에 각각 형상비(H/R)가 4와 2인 형태로 채워져 있을 경우 수직원관 내로 유입되는 작동유체의 온도를 $-10^{\circ}C$, 유량을 10 liter/min로 고정시킨 후 유동방향을 상향과 하향으로 변화시켰을 경우 시간경과에 따라 나타나는 물의 응고형상, 수직원통의 온도분포, 수직원관의 온도분포, 축열량에 대한 열전달현상을 실험적으로 규명한 것이다. 축열조내 물의 온도분포는 초기온도가 $7^{\circ}C$인 경우 냉각과정중 축열조내 상부가 하부보다 높고 시간경과 후 물의 최대밀도점인 $4^{\circ}C$ 이하에서는 축열조 하부가 상부보다 높으며, 초기온도가 $4^{\circ}C$와 $1^{\circ}C$인 경우는 물의 밀도값이 최대점인 $4^{\circ}C$ 이하이므로 실험시작 초기부터 하부가 상부보다 온도분포가 높게 나타났다. 응고과정 시에는 동일한 초기온도 하에서 작동유체의 유동방향이 상향일 경우가 하향일 경우보다 축열조내 자연대류 유동이 활발하여 액상의 평균온도는 빠르게 강하되고 수직원관 외벽면의 상 하부 온도차이도 적으며, 응고형상은 축열조내 물의 초기온도가 $7^{\circ}C$와 $4^{\circ}C$ 일 때 상 하부에서 고르게 진전된다. 축열조내 물의 초기온도가 $1^{\circ}C$인 경우는 전도열전달의 영향이 지배적이므로 응고층의 생성은 작동유체 유동방향으로 형성되어진다. 축열량은 형상비에 관계없이 초기온도가 높을수록 크게 나타났으며, 동일한 초기온도 하에서도 작동유체의 유동방향이 상향으로 유입될 경우가 하향에 유입되는 경우보다 시간경과 후 크게 나타났다.