An Evaluation of Airtightness Performance and Analysis of Energy Savings Potential in Apartment Housing

공동주택의 기밀성능 평가 및 에너지 절감효과 분석

  • Leigh, Seung-Bok (Department of Architectural Engineering, Sung Kyun Kwan University)
  • Published : 1995.12.31

Abstract

Since the using of heating energy associated with infiltration is significant in a building, the efforts to minimize the infiltration while ensuring minimum ventilation rates for various types of occupancy will be beneficial. In constrast to that many efforts have been made to reduce heat loss by improving thermal resistance of building envelope, little has been tried to reduce heat loss from infiltration. For achieving such an objective, measurement of air leakage rate will be pre-requisite as a diagnostic tool. A blower door system, a depressurization/pressurization method, was employed and it demonstrated a good potential for measuring airtightness performance of residential buildings. Based on the test results, annual energy savings for residential heating was estimated by reducing infiltration to a level of reasonably airtight or to a level of ASHRAE Standard 62-1989 for minimum ventilation.

지금까지 우리는 건물분야에서의 합리적인 에너지 사용을 위하여 건물외피의 단열성능을 향상시킴으로써 열손실을 줄이려는 데에 주력하여 왔으며, 침기로 인한 열손실을 줄이려는 노력은 상대적으로 미흡하였다. 그러나, 침기로 인한 난방에너지의 소비가 상당량에 이르는 것으로 조사됨으로써 재실형태에 따라 최소환기기준을 만족시키면서 침기에 의한 불필요한 에너지의 손실을 줄이려는 노력이 매우 유효한 것으로 평가되고 있다. 실제로 침기에 의한 불필요한 에너지의 낭비가 얼마나 되는가를 평가하기 위해서는, 건물에서의 침기율을 정확하게 측정할 수 있는 방법이 전제되어야 한다. 본 연구에서는 감압/가압법의 일종인 Blower Door System을 사용하여 공동주택에서의 기밀성능을 측정, 평가함은 물론 측정결과를 토대로 합리적인 수준까지 기밀화할 경우 난방에너지의 절약가능성에 대하여 추정하였다.