A Thermal Analysis for the Underground Power Transmission Cable by a Water Pipe Cooling Method with Trough in Tunnel

전력구트라프간접수냉방식에서의 지중송전케이블에 대한 열해석

  • Park, Man-Heung (Power Engineering Research Institute, Korea Power Engineering Company)
  • 박만흥 (한국전력기술주식회사 전력기술개발연구소)
  • Published : 1995.12.31

Abstract

The thermal analysis is accomplished with the route for the underground power transmission system which adopts the water pipe cooling with trough in tunnel. As a result, in case of a cooling system based on a refrigerator, the optimum condition for the flow rate of cooling water and the air velocity are calculated as the $2{\sim}3{\ell}/s/pipe$ and $1{\sim}2m/s/fan$, respectively. On the other hand, in case of cooling tower the optimum condition for them are calculated as the $2{\sim}3{\ell}/s/pipe$ and 6 m/s/fan, respectively. But the cooling system based on a cooling tower has the problem of enlarging the size of cooling fan and suppressing the labor of operator in tunnel. Therefore, to meet all the cooling conditions for a given cooling section, the cooling system based on a refrigerator is more acceptable.

원활한 전력공급을 위해 지중송전케이블에서 발생된 열을 제거하기 위한 방법으로 전력구트라프간접수냉방식이 적용된 지중송전계통에 대한 각 주요 구성요소의 열해석을 수행하였다. 열해석을 수행한 결과, 주어진 조건에서 냉동기가 채택된 냉동장치에서는 냉각수유량은 $2{\sim}3{\ell}/s/pipe$, 팬에 의한 풍속은 $1{\sim}2m/s/fan$인 경우에 지중송전계통의 원활한 전력공급을 위한 냉각계통의 최적조건으로 계산되었다. 반면에 냉각탑만을 설치한 경우에는 냉각수유량 및 풍속이 각각 $2{\sim}3s/pipe$ 및 6 m/s/fan이 최적조건으로 계산되었다. 그러나 냉각탑만이 설치된 경우에는 풍속이 너무 커져서 용량이 큰 팬의 설치 및 전력구내에서 작업자의 작업조건에 적합하지 않다. 따라서 본 연구의 주어진 조건하에서 지중송전계통의 냉동계통은 냉동기가 설치된 냉동장치가 바람직하다.