Korean Journal of Air-Conditioning and Refrigeration Engineering (설비공학논문집)
- Volume 6 Issue 3
- /
- Pages.315-324
- /
- 1994
- /
- 1229-6422(pISSN)
- /
- 2465-7611(eISSN)
Design of an Aquifer Thermal Energy Storage System(II) : Thermal Analysis
지하대수층을 이용한 축열시스템의 설계(II) : 열해석
Abstract
The energy recovery efficiency(ERE) of an aquifer thermal energy storage system was calculated using curvilinear coordinate. The results of the calculation were compared with the experimental results, and agreed within 11% of the discrepancy. The variation of ERE was investigated as a function of the underground water natural velocity, the amount of the stored energy, and period of the energy recovery. The slower the natural velocity and shorter the recovery period, the higher ERE was yielded. Also it was found that increase in the amount of energy storage yields higher ERE, and carries out less influential ERE to the natural velocity. Reiterative usage of the aquifer as a thermal storage tends to gradually increase ERE. The result of this study implements that the aquifer thermal energy storage system is suitable for large cooling/heating loads, such as district cooling/heating.
Keywords