Cold Energy Storage System Using Direct Contact Heat Transfer

직접 접촉식을 이용한 빙축열 시스템

  • 이윤표 (한국과학기술연구원 기계공학부) ;
  • 윤성영 (한국과학기술연구원 기계공학부) ;
  • 이춘식 (한국과학기술연구원 기계공학부)
  • Published : 1994.08.01

Abstract

In this study, experimental investigations to find cold energy storage performance have been made for two different temperatures at condenser. Temperatures at inlet and outlet of condenser were measured to calculate global heat transfer coefficient of direct contact method in our cold energy storage system. Also storage performance by direct contact method was compared with that of Ice-On-Coil type ice storage which was calculated by analytic solution. Results show that, in the case of $-8.0^{\circ}C$ at condenser inlet, heat transfer coefficient of direct contact method is 3.25 times higher than that of conventional method and COP of system is improved by using R141b as refrigerant which produces gas hydrate and has higher phase change temperature than $0.0^{\circ}C$.