Effects of Oil and Internally Finned Tubes on the Performance of the Air-Conditioning Unit

전열관 형상과 냉동기유 효과를 고려한 공조기기의 성능예측

  • 윤점열 (금성사 생활시스템 연구소) ;
  • 이관수 (한양대학교 기계공학과) ;
  • 이동진 (금성사 생활시스템 연구소)
  • Published : 1994.11.01

Abstract

Computer simulation model for predicting more accurately the heat transfer performance of the evaporator and condenser which have significantly affected on the performance of air-conditioner has been suggested. In this model oil and micro-fin tube used in a actual unit are considered to simulate the more realistic case. The effects of oil and micro-fin tube on the performance of an air-conditioner have been investigated. It is found that the present model requires higher pressure than the existing model due to the characteristics of the tube considered. However, it turns out that the present model is very close to an actual cycle. As the amount of oil inside the tube increases, condensation heat transfer coefficient shows a linear decrease irrespective of a kind of oil, while evaporation heat transfer coefficient increases slightly in the oil with low viscosity and decreases exponentially in the oil with high viscosity. Pressure drop in both evaporator and condenser increases linearly irrespective of a kind of oil. It is also found that the effect of the variation of oil concentration on the magnitude of two-phase region is negligible.

Keywords